Part Number 3363SMG4-30-208VAC60-2 Specification |
|||
---|---|---|---|
Part Number: 3363SMG4-30-208VAC60-2 | Manufacturer: Eaton Corporation | Item Name : circuit breaker | |
NSN: 5925-00-605-9319 | FSC : 5925 Circuit Breakers | CAGE Code: 74193 | |
Alternate P/N : 3363SMG430208VAC602 |
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-605-9319 Item Description: Circuit Breaker | 5925 | 006059319 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | U | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
3363smg4-30-208vac60-2 | 5 | 9 | 5 |
MRC | Criteria | Characteristic |
---|---|---|
AAQL | NULL | NULL |
ADAQ | BODY LENGTH | 5.250 INCHES NOMINAL |
ADAT | BODY WIDTH | 3.000 INCHES NOMINAL |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 4.359 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 4.359 INCHES NOMINAL |
AJEC | BOSS HEIGHT | 0.219 INCHES NOMINAL |
AKPX | POLE QUANTITY | 3 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 30.0 AMPERES AC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 208.0 AC ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 5.500 MINIMUM AT 200 PCT ALL LOCATIONS AND 10.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |
ADTV | CASE MATERIAL | PLASTIC |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.000 INCHES NOMINAL |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.190 INCHES NOMINAL |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.000 INCHES NOMINAL |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 3.513 INCHES NOMINAL |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND MOISTURE RESISTANT |
PKWT | UNPACKAGED UNIT WEIGHT | 1.750 POUNDS |
Related NSN Components to 3363SMG4-30-208VAC60-2 |
|||
---|---|---|---|
336 0.065 SS 12 | 336-000-0004 | 336-00001 | 336-00010 |
336-00012 | 336-00014 | 336-00015 | 336-00016 |
336-00017 | 336-00020 | 336-00021-00 | 336-0003-00 |
336-0003-010 | 336-000400 | 336-00044-00 | 336-0005-001 |
336-000500 | 336.000IC | 336-001-202-0 | 336-001-203-0 |
336-001-303-0 | 336-001-304-0 | 336-001-404-6 | 336-001-503-6 |
All Orders are Fulfilled in the U.S.A.
All shipments must comply with U.S.A export laws.
No exceptions.
The only independent distributor
with a NO CHINA SOURCING Pledge
“We Proudly Support Intrepid Fallen Heroes Fund that serves United States Military Personal experiencing the Invisible Wounds of War : Traumatic Brain Injury (TBI) and Post Traumatic Stress (PTS). Please visit website (www.fallenheroesfund.org) and help in their valiant effort”.
Don’t forget That We offer 24/7 Service, Competitive Prices, and Fast Deliveries. We Hope You'll Make Us Your One-Stop Purchasing Solution!
Request for Quote