Part Number KH 36125 Specification |
|||
---|---|---|---|
Part Number: KH 36125 | Manufacturer: Schneider Electric Usa Inc | Item Name : circuit breaker | |
NSN: 5925-01-043-5812 | FSC : 5925 Circuit Breakers | CAGE Code: 51918 | |
Alternate P/N : KH36125 |
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-01-043-5812 Item Description: Circuit Breaker | 5925 | 010435812 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | A | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
KH 36125 | 5 | 2 | 3 |
MRC | Criteria | Characteristic |
---|---|---|
ADAQ | BODY LENGTH | 8.000 INCHES NOMINAL |
ADAU | BODY HEIGHT | 4.656 INCHES NOMINAL |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 6.875 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 7.125 INCHES NOMINAL |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.500 INCHES NOMINAL |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 145.0 ALL LOCATIONS |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 6 COMPRESSION |
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
ADAT | BODY WIDTH | 4.500 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.500 INCHES NOMINAL |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.203 INCHES NOMINAL |
AJEC | BOSS HEIGHT | 0.136 INCHES NOMINAL |
AKPX | POLE QUANTITY | 3 |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 125.0 AMPERES AC ALL LOCATIONS AND 125.0 AMPERES DC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 25000.0 AC ALL LOCATIONS AND 10000.0 DC ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 150.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 250.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
Related NSN Components to KH-36125 |
|||
---|---|---|---|
KH 0004 | KH-06411-03 | KH-06NPT-L-1112-16X-S0597 | KH 1001 CRX |
KH-102-6 | KH-106-19 | KH-106-22 | KH-106-23C |
KH-106-27D | KH-106-6 | KH-137-4A | KH-137-5 |
KH-139-BL | KH-15 | KH-1K | KH-2024 |
KH 2030 | KH-212-0 | KH-2271-1A | KH-2540-101-585 |
KH-302 | KH-31036-25 | KH-3553 | KH 36150 |
All Orders are Fulfilled in the U.S.A.
All shipments must comply with U.S.A export laws.
No exceptions.
The only independent distributor
with a NO CHINA SOURCING Pledge
“We Proudly Support Intrepid Fallen Heroes Fund that serves United States Military Personal experiencing the Invisible Wounds of War : Traumatic Brain Injury (TBI) and Post Traumatic Stress (PTS). Please visit website (www.fallenheroesfund.org) and help in their valiant effort”.
Don’t forget That We offer 24/7 Service, Competitive Prices, and Fast Deliveries. We Hope You'll Make Us Your One-Stop Purchasing Solution!
Request for Quote